Cabinets and/or panels are available in many types,
sizes, colors and methods of construction. They
can be
outfitted with many different accessories depending on your needs. In general, each
cabinet is custom engineered, to meet many different parameters. Care must be taken to
specify a cabinet or panel that meets all your needs and specifications. This application
note is provided as a guide to prepare a specification and needs to be provided along with
complete equipment listing of all systems being mounted in the cabinet.
Cabinet Location:
Cabinets are mounted either indoors or outdoors. Indoor
cabinets can be mounted in a control, electrical or switchgear room. Outdoor cabinets may
be mounted close to or on the machine deck exposed to the elements. Indoor cabinets are
normally painted steel and meet Nema 12 requirements. Outdoor cabinets can be painted
steel for Nema 4 or Stainless Steel for Nema 4x requirements.
Indoor___ Outdoor Nema4___ Nema4___
Environment:
Both indoor and especially outdoor cabinet environments
need to be looked at for special environmental concerns and requirements. Temperature is a
common issue for outdoor cabinets. Both the annual temperature extremes of the proposed
cabinet location and the heat generating capacity of the equipment to be installed in the
cabinet must be carefully looked at. Heating and/or Air Conditioning will be installed as
required.
Min.Temp ______ C/F. Max. Temp_______C/F
Type and Manufacture of Cabinet:
Cabinets come in two (2) basic types, Solid and Modular.
Solid Cabinets have welded seams where modular cabinets are bolted together. Solid
cabinets will be generally be used outdoors and modular cabinets indoors. In some cases a
customer may have a preference between manufactures.
Solid___ Modular___ Manufacture___________
Access:
The location that the cabinet is to be installed in needs
to be looked at carefully as to access for maintenance and repair of the installed
equipment. In general most cabinets have access front and rear. In some cases where a
cabinet is to be mounted against a wall only side or front access is available. We always
recommend Front and Back Access as any other type is difficult and expensive unless
absolutely required. If side access is necessary, specify which side as if you are looking
from the front.
Front & Back___ Front & L/R___ Front Only___
Dimensions or Size:
Size is in the end determined by the installed equipment
and required options. In most cases a desired size is specified and then will be changed,
as engineering requires. Other existing cabinets and the desire to have the installed
equipment close to eye height normally determine height. Height will normally be between
78" (2000 mm) and 82" (2100 mm). Width will be determined by available space and
the installed equipment and will be 19" EIA, 24" (610 mm) or 36" (914 mm).
Depth is determined by the depth of the installed equipment and will be either 26"
(650 mm) or 34" (850 mm).
Height_______Width________Depth_______
Power Distribution:
Power distribution is recommended and is usually
provided. A power distribution panel with breakers and two (2) accessory power outlets
will be provided. Lighting will be provided in the top of the panel for ease of
maintenance. Top or Bottom power and wire entry to the cabinet needs to be specified along
with input voltage.
Top___ Bottom___
110 VAC___ 220 VAC___
Intermediate Terminal Blocks:
Intermediate terminal blocks are a required feature on
most cabinets. This allows for all the pre-wiring of the installed equipment to take place
at the cabinet shop. Only power and external wiring need to be attached to the terminal
blocks. A listing of the equipment to be installed, installed transducers, recorder
outputs and required relays along with a percentage of spare terminal blocks to be
supplied is required. As an alternate, direct wiring to the installed equipment can be
accomplished.
Intermediate Terminals___ Direct___
2-Wire Transducers _____
3-Wire Transducers _____
Recorder Outputs _____
Relay's Required _____
% Spares Required _____
Paint and Color:
The specific exterior paint color of the cabinet may be
optionally specified to meet existing cabinet specifications or preferences. Any color
other than standard OEM colors must be specified in advance. Non stock paints will effect
price and lead times.
Standard Gray___ Specified
______________
Doors:
Doors need to be specified as either left handed or
right-handed.
Left Handed___ Right Handed___
Accessories:
Smoke Detector___
Heat Sensor___
Transportation Eyebolts___
Door Locks___
Air Conditioning___
Heating___
Fan___ w/Filter___
Glass Front Door___
Air Purging___
Drawing Package:
Please see our standard drawing package as a starting
point of drawing package options. Drawings can be provided in AutoCAD Format (Standard) as
well as Intergraph. Drawings can be provided in prints, reproducible and digital formats.
AutoCAD___ Intergraph___
Mechanical Drawing Package___
Electrical Drawing Package___
Field Transducer Interconnect___
Mechanical Drawing Package___
Electrical Drawing Package___
Field Transducer Interconnect___
|