CMCP-560A Isolated RTD Temperature Monitors


RTD Temperature Monitor

Features:

  • Low Cost

  • Small Size

  • DIN Rail Mount

  • RTD Input

  • 4-20 mA Output

  • Fault Detection

  • Buffered Transducer Output

  • Filter Option

  • Alert and Danger Alarms

  • Trip Multiply

  • Remote Reset

  • CSA & UL Approved

  • Class I Division II

Approved

Temperature Monitor Data Sheet PDF Format


Description:
The CMCP560A Isolated RTD Temperature Monitors are compatible with 100 Ohm Platinum RTD inputs, and they provide a 4-20 mA output proportional to the overall measurement. Each unit provides power for the associated transducer, processes the signal to determine overall amplitude, and outputs a 4-20 mA dc current that is proportional to a user specified range such as 0-250 Deg. F. Combining monitors with an existing PLC or DCS system results in a high density, low cost monitoring system. The alarm feature functions as a complete single channel monitor that includes alert and danger alarms, and output relays.

Buffered Output:
A BNC connector mounted on the front of the unit provides access to the buffered transducer output signal. This includes both the unfiltered vibration signal, and the DC bias voltage. Portable test equipment or analyzers like SKF-CM's MicrologTM can be connected to this output without disturbing other system outputs.

Fault Detection:
On board fault detection circuitry continuously monitors the transducer for normal operation. If a fault occurs, the output current is reduced to 2 mA to indicate the fault to the readout system. A red LED on the front of the unit is turned on to provide a local indication of the fault.

Alarms:
The CMCP560A Isolated RTD Temperature Monitors have two independent set points, with LED alarm indicators and output relay contacts (Alert and Danger). Set points are adjustable via potentiometer, from 0 to 110% of full scale. Each has an adjustable delay of 1 to 10 seconds. Relay contacts can be independently configured by the user for either Normally Open (NO) (Standard) or Normally Closed (NC) operation. Relays are normally de-energized and can be configured for latching or non-latching (standard) operation. Latched alarms may be reset locally or by remote contact closure. SPST Relay contacts are rated 5 Amps @ 30 Vdc or 250 Vac for resistive loads. The monitors also have set point multiplication of 3X via contact closure (2X available).

Displays And Assemblies:
Various display options, NEMA and explosion-proof enclosures, and assembled multi-channel systems are available. Consult your sales representative.

Electrical Specifications:
Power: +24 Vdc @ 45 mA max. (30 mA typical at 2 full scale output). Reverse polarity and transient protection   included.(With the Alarm/Relay option installed: 75 mA max.)
Frequency Response (Without optional filters): (-3 dB) 2 Hz to 20 kHz.
Buffered Output: BNC Connector 0-20 kHz.
Accuracy: 5.0 % of Full Scale Range.
Output: 4-20 mA proportional to the full scale range.
Maximum Load: 600 Ohms Resistive.
Case: Isolated.

Environmental Specifications:
Operating Temp.:
-20oC to +80oC (-4oF to +176oF).
Storage Temp.: -55oC to +125oC (-67oF to +257oF).
Relative Humidity: 0 - 95% Non-Condensing.

Mounting:
32 mm (G style) or 35 mm (T style) DIN Rail.

Ordering Example:

To order a RTD temperature monitor that accepts input from a 100 Ohm Platinum RTD, with a Full Scale of 0-250 Deg. F, specify Part Number: CMCP560A-100P-01.

NOTES:

1.The Full Scale option specified at order entry is used by the factory for initial calibration. However, several other ranges can be jumper selected in the field.

2.Transducer and Full Scale options not listed in the above table are available. Contact your sales representative.


CMCP560A Isolated RTD Temperature Monitor
CMCP560A-(aaaa)-(bb)

(aaaa) Input
100P, 100 Ohm Platinum RTD

(bb) Full Scale
01, 0-250 oF
02, 0-350 oF
03, 0-500 oF

51, 0-120 oC

52, 0-175 oC

53, 0-260 oC