Navigate to the STI Vibration Monitoring Inc. homepage

TC Temperature Transmitter/Monitor

CMCP565 Thermocouple Temperature Transmitter/Monitor

STI
$0.00
CMCP565 Data Sheet
Choose your options:
Sensor Input
Sensor Input:
Output Range
Output Range:
Alarm Module
Alarm Module:
Product Code: CMCP565
CMCP500 Transmitter Approval Label
  • Thermocouple Input
  • Temperature Output
  • Transmitter or Monitor
  • Voltage Detection
  • Type J and K Standard
  • 4-20 mA Output
  • 2 Buffered Outputs
  • 5 Selectable Ranges
  • Fault (OK) Detection
  • CSA & UL C1,D2
  • DIN Rail Mount
The CMCP565 Isolated Thermocouple Temperature Transmitters are compatible with J and K type thermocouple inputs, and they provide a 4-20 mA output proportional to the overall measurement. Each unit processes the signal to determine overall amplitude, and outputs a 4-20 mA dc current that is proportional to a user specified range such as 0-250 Deg. F. Combining transmitters with an existing PLC or DCS system results in a high density, low cost monitoring system.

Alarms relays and trip multiply are available with the Monitor version.

Alarms - The CMCP500A Series Monitors have two independent set points, with LED alarm indicators and output relay contacts (Alert and Danger). Set points are adjustable via potentiometer, from 0 to 110% of full scale. Each has an adjustable delay of 1 to 10 seconds. SPST Relay contacts are rated 5 Amps @ 30 Vdc or 250 Vac for resistive loads.

CMCP500 Monitor Approval LabelRelay contacts can be independently configured by the user for either Normally Open (NO) (Standard) or Normally Closed (NC) operation. Relays are normally de-energized and can be configured for latching or non-latching (standard) operation. Latched alarms may be reset locally or by remote contact closure.

Trip Multiply - The monitors have set point multiplication of 3X via contact closure (2X available). To avoid tripping the alarms during machine start-up.
Custom Input and Output Configurations Available On Request
Buffered Output:
A BNC connector mounted on the front of the unit provides access to the buffered transducer output signal. This includes both the unfiltered vibration signal, and the DC bias voltage. Portable test equipment or analyzers like SKF-CM's MicrologTMcan be connected to this output without disturbing other system outputs.
Fault Detection:
On board fault detection circuitry continuously monitors the transducer for normal operation. If a fault occurs, the output current is reduced to 2 mA to indicate the fault to the readout system. A red LED on the front of the unit is turned on to provide a local indication of the fault.

Documents Available:
CMCP565 Data SheetCMCP565 ManualCMCP565 UL/CSA CertificateCMCP565 CE Certificate

Electrical Specifications:
Input: Type J or K
Power: +24 Vdc @ 45 mA max. (30 mA typical).
Protection: Reverse polarity and transient protection included.
Accuracy: 0.5 % of Full Scale Range.
Output: 4-20 mA proportional to the full scale range.
Maximum Load: 600 Ohms Resistive.
Case: Isolated.
Range: English, 0 to 250° F, or
Metric, -17.7 to 121° C
Fault Indication: Green LED and 4-20 mA < 2mA

Relay Module:
Alarms: OK, Alert and Danger
Alarm Setpoints: Alert and Danger Adjustable 0 to 110% FS.
Trip Multiply: 2X or 3X on Contact Closure.
Alarm Relays: OK, Alert and Danger.
Form C, SPDT, 5A @ 30 VDC or 250 VAC.
Latching or Non-latching, Selectable.
Time Delay: 0.1, 1, 3, 6 or 10 Seconds, Selectable.
Alarm LED's: Alert = Yellow, Danger = Red.
Display Outputs: 0-5 VDC for Current Value, Alert Setpoint and Danger Setpoint.

Environmental Specifications:
Operating Temp.: -20°C to +80° C (-4° F to +176° F).
Storage Temp.: -55°C to +125° C (-67° F to +257° F).
Relative Humidity: 0 - 95% Non-Condensing.

Physical:
Mounting: 32 mm (G style) or 35 mm (T style) DIN Rail.
Size: Transmitter 1.0" Wide x 3.11" High x 3.95" Deep
w/Relay Module 1.6" Wide x 3.11" High x 3.95" Deep