Tech Note 116: Electro-Mechanical Velocity Sensors
Last Updated: 05/10/2017

Electro-Mechanical Velocity SensorsThe base model CMCP535-100V vibration transmitter is designed for use with an IEPE (Integrated Electronics Piezo Electric) type velocity sensor. This type of sensor requires constant current sensor power from the transmitter, and outputs both a vibration velocity signal (typically 100 mV/ips) and a dc bias voltage. The dc bias is monitored by the transmitter and used to determine the “OK” status of the sensor. For this type of sensor the buffered output mirrors the input, i.e.: for a 100 mV/ips input, the buffered output will also be a nominal 100 mV/ips.

A "CMCP535-xxxEV" version is used when the sensor is not the IEPE type, but rather a self-generating (Electro-Mechanical) type velocity sensor. This type of sensor does not require power from the transmitter and does not output a dc bias voltage, so monitoring the “OK” status of the sensor requires different internal input circuitry in the transmitter. A result of this is that there are sensitivity differences at the buffered output. Your customer is using a CEC velocity sensor that is a self-generating (electro-mechanical-velocity) type sensor with a nominal sensitivity of 135 mV/ips. Note that the actual sensitivity of this type of sensor can vary from the nominal value depending on loading across its terminals. When this type of sensor is connected to the CMCP535, the transmitter creates its own dc bias voltage to allow for sensor “OK” status detection; a consequence of which is that the output sensitivity is attenuated. For self-generating sensors with nominal sensitivities from 125mV/ips to 500 mV/ips, this attenuation is normalized so that the sensitivity realized at the buffered output is a nominal 100 mV/ips. An additional factor to consider is that the output impedance at buffered output is 1 kOhm. When the input impedance of any instrument connected to the buffered output is less than 1M Ohm, additional attenuation will result.
If this output is to be connected to a readout device, a nominal value of 100 mV/ips should be used for any calculations.




Was this article helpful?

Comments:
 

Related Articles
 > Tech Note 101: Wiring CMCP1100 (ICP) Accelerometers
 > Tech Note 102: Powering – 24 VDC Eddy Probes
 > Tech Note 103: Accelerometer Powering with CCD Diode
 > Tech Note 104: Wiring Relays with Common Alarms
 > Tech Note 105: Reversing Normal Thrust Direction CMCP545(A)
 > Tech Note 106: Recalibrating CMCP505 Digital Displays >01/01/07
 > Tech Note 108: Installation of Accelerometer Extension Cables
 > Tech Note 107: Recalibrating CMCP505 Digital Displays <01/01/07
 > Tech Note 109: Troubleshooting 500 Series Transmitters
 > Tech Note 110: Troubleshooting CMCP420VT(T)
 > Tech Note 111: CMCP510 Display Calibration
 > Tech Note 112: Vibration Severity Level ISO 10816-1
 > Tech Note 113: CMCP420VT(T) Compliance
 > Tech Note 114: Double Integration of Vibration Signals
 > Tech Note 115: Shunt Resistors
 > Tech Note 117: ISO Standard 10816-3
 > Tech Note 118: What We Need to Know!
 > Tech Note 119: CMCP420VT Buffered Output
 > Tech Note 120: CMCP575 Tachometer Precision Calibration
 > Tech Note 121: Magnetic Bases for Accelerometers
 > Tech Note 122: Double Integration
 > Tech Note 123: Calculating Transmitter Ranges
 > Tech Note 124: Cable Grounding (Isolated and Non-Isolated Shields)