Tech Note 120: CMCP575 Tachometer Precision Calibration
Last Updated: 07/12/2017

CMCP575 Tachometer Precision CalibrationCMCP575 Speed Transmitters labeled sold after 1/1/2009 feature the new Smart Touch technology which allow users to calibrate the transmitter within 10% of the frequency span simply by depressing the Zero and Span buttons on the front of the unit while inputting the applied frequency range. In order to accurately set the transmitters 4-20mA output additional steps need to be taken. To calibrate the transmitter the following test equipment is required.


Signal Generator
Digital Volt Meter
24 VDC Power Supply


To begin, connect test equipment according to the diagram below and turn on power supply and signal generator and wait 30 seconds for the transmitter to power up and run through the self-check mode.


Operating Speed Calculation: (RPM 60) x Events Per Revolution
Example: 3600 Max RPM Shaft with 1 Keyway Acting as Sensor Target: (360060) x 1 = 60Hz
300 Max RPM Shaft with a 36 Tooth Gear Acting as Sensor Target: (30060) x 36 = 180Hz


The CMCP575 range should exceed the maximum operating speed by a 10% minimum. General calibration ranges are 0-2,500 RPM, 0-5,000 RPM and 0-10,000 RPM though range can be calibrated to any range.


To Adjust the Zero Scale (4mA):
1. Input the minimum frequency level (usually 0 Hz) with an amplitude greater than 50mV
2. Depress the Zero button on the front of the CMCP575, Zero Light will start flashing.
3. Use digital multimeter (DVM) in mA mode to measure the 4-20mA output.
4. If necessary, adjust the Zero screw until the DVM reads 4.00mA


To Adjust for Full Scale/Span Calibration (20mA):
1. Input the maximum calculated frequency level with an amplitude greater than 50mV.
2. Depress the Span button on the front of the CMCP575, Span Light will start flashing.
3. Use digital multimeter (DVM) in mA mode to measure the 4-20mA output.
4. If necessary, adjust the Span screw until the DVM reads 20.00mA


Note:
In order for the CMCP575 to operate the input signal must be greater than 10mV. If the target area does not provide a signal greater than 50mVrms the CMCP575 will not operate correctly.


If the CMCP575 does not provide a steady output while in normal operation the hysteresis may need to be adjusted. While the machine is running at a continuous speed start with the hysteresis screw fully counter clockwise. Turn the adjustment screw clockwise a quarter turn at a time until the output is steady. Verify 4-20mA output calibration after any adjustments.


CMCP575 Calibration Setup



Was this article helpful?

Comments:
 

Related Articles
 > Tech Note 101: Wiring CMCP1100 (ICP) Accelerometers
 > Tech Note 102: Powering 24 VDC Eddy Probes
 > Tech Note 103: Accelerometer Powering with CCD Diode
 > Tech Note 104: Wiring Relays with Common Alarms
 > Tech Note 105: Reversing Normal Thrust Direction CMCP545(A)
 > Tech Note 106: Recalibrating CMCP505 Digital Displays >01/01/07
 > Tech Note 108: Installation of Accelerometer Extension Cables
 > Tech Note 107: Recalibrating CMCP505 Digital Displays <01/01/07
 > Tech Note 109: Troubleshooting 500 Series Transmitters
 > Tech Note 110: Troubleshooting CMCP420VT(T)
 > Tech Note 111: CMCP510 Display Calibration
 > Tech Note 112: Vibration Severity Level ISO 10816-1
 > Tech Note 113: CMCP420VT(T) Compliance
 > Tech Note 114: Double Integration of Vibration Signals
 > Tech Note 115: Shunt Resistors
 > Tech Note 116: Electro-Mechanical Velocity Sensors
 > Tech Note 117: ISO Standard 10816-3
 > Tech Note 118: What We Need to Know!
 > Tech Note 119: CMCP420VT Buffered Output
 > Tech Note 121: Magnetic Bases for Accelerometers
 > Tech Note 122: Double Integration
 > Tech Note 123: Calculating Transmitter Ranges
 > Tech Note 124: Cable Grounding (Isolated and Non-Isolated Shields)